The HP101U Series ConventionalFire Alarm Control Panel is a 24 volt,
four to sixteen-zone, Class B, Conventional Fire Alarm Control Panel. Designed exclusively to meet the latest market requirements and future ULC codes, the highly cost-effective IDC1000 Series can be used in a variety of low- to mid-sized applications.
Conventional Fire Alarm Panel 4 Zones
Four Zones Style B (ClassB)Initiating Device Circuits (IDCs).
All zones accept two-wire smoke detectors and any normally-open contact devices.
Zones 1 – 4 configured as generalalarm zones.
All circuits are power-limited and supervised, meeting the latest ULC
requirements using fuse less technology.
Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits
(NACs).
NACs may be programmed: Silence able.- Non-Silence able.- Auto –
Silence (5 to 20 Minutes).
1.25 amps of NAC power& 3.0 amps of totalsystem power.
Alarm, Trouble and Supervisory, Form-e relays standard. & 24-volt operation.
Resettable four-wire smoke detector power @ 500 mA.Non-resettable power @ 500 mA.
Integral battery charger capable of charging up to 18 AH batteries
(batteries over 4 AH require use of the extemal battery back box,or ULC
listed equivalent).